Check-Out Procedure For Hard-Wined Zones
After installation of all hard-wired devicesis completed,euch partition of the
setity systemshouldbe checked,as follows.
1. Make certain that all devicesand sensors connectedto the hard-wired
zonesare not in a faulted state. Doors and windows with contactsshould
be closed,PIRs should be covered(use a clothto mask them temporarily if
necessary).
2. Plug in the AC Transformer if you have not already done so..
3. With all hard-wired zones intact, the Alpha keypad connectedto the
systemshould display
ml
If the followingis displayed,
~,
press the [*] key to display the faulted zone(s). Restore any faulted
zone(s)as necessary(also make sure that you have connecteda 2000 ohm
EOL resistor acrossthe terminals ofunused zones).
When the DISARMED...READY TO ARM messageis displayed, you can
proceedto the nextstep.
4. Fault and then restoreevery contactor sensoron eachzone individually to
ensure that it is being monitored by the system. Each time a zone is
faulted, the keypad should display the number of the faulted zone.When
eachzone is restored,the READY TO ARM messageshould appear again.
If somehard-wired zones have been assignedto partition 1 and others to
partition 2, you will need to observe the keypad hi the appropriate
partition as eachzonein that partition is faulted and restored.
5. When you get the proper displays on the keypad(s),the hard-wired zones
in the systemare functioningproperly.
6. Unplug the AC transformer.