AUX. POWER
OUTPUT
10.5-13.8VDC
600mA MAX.
INTERRUPTS
FOR FIRE
ALARM RESET
NOTE:
KEYPAD(S)
CURRENT (IN
BOTH
PARTITIONS)
AND ALL
OTHER
DEVICES
DRAWING
POWER FROM
TERMS 4 & 5
MUST BE
INCLUDED IN
AUX CURRENT
DRAIN
CALCULATIONS
OPTIONAL
FOR UP TO 24 ADDITIONAL ZONES
(ONE FROM EITHER OR BOTH GROUPS)
ADEMCO 5881* Type
RF RECEIVER
WIRELESS ZONES
5881L: UP TO 8
5881M: UP TO 16
5881H: UP TO 24
* 5882 IN CANADA
ADEMCO No. 4219
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
-OR-
ADEMCO No. 4229
WIRED EXPANSION/RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
OUTPUT RELAYS)
-OR-
ADEMCO No. 4204 RELAY MODULE
(4 OUTPUT RELAYS)
BLK
RED
GRN
YEL
123456789101112131415161718192021 22 23 24 25
EARTH GROUND
SEE
INSTRUCTIONS
FOR PROPER
GROUNDING
TELEPHONE WIRING
(VIA RJ31X* JACK AND DIRECT
CONNECT CORD)
*CA38A IN CANADA
DOC LOAD NO.: 3
FOR CONNECTION OF
OPTIONAL 4285 VOICE MODULE
TO PHONE TERMINALS, SEE
INSTRUCTIONS.
REMOTE KEYPADS
EACH PARTITION CAN
USE 4127, 4137AD,
5137AD, 6127, 6128, 6137,
6138, OR 6139 KEYPADS.
LOCAL PROGRAMMING
MUST BE DONE WITH A
5137AD OR 6139 CON-
NECTED TO PARTITION 1,
BUT NEED NOT REMAIN
IN THE SYSTEM.
OPTIONAL 4285 VOICE
MODULE CONNECTS TO
PARTITION 1 KEYPAD
TERMINALS (SEE
INSTRUCTIONS).
BLACK: KEYPAD GROUND (–) RETURN
RED: KEYPAD PWR (+)
GREEN: DATA IN FROM KEYPAD
YELLOW: KEYPAD DATA OUT
▲
▲
REMOTE
KEYPAD
PARTITION 1
}
WARNING:
TO PREVENT RISK OF
SHOCK, DISCONNECT TELEPHONE LINE
AT TELCO JACK BEFORE SERVICING
THIS UNIT.
CHARGING
VOLTAGE
13.8VDC
BATTERY
12V, 4AH
–
+
–
+
CONNECTOR
TABS
PLUG-IN TRANSFORMER
16.5VAC, 25VA (e.g. ADEMCO
No. 1321, USE No. 1321CN IN
CANADA)
TO 110VAC
UNSWITCHED
OUTLET (24HR)
–
+
BLK
RED
GRN
YEL
TO TERM 4
TO TERM 5
TO TERM 6
TO TERM 7
BLK
RED
GRN
YEL
AND/OR
SET RECEIVER’S
DIP SWITCH FOR
DEVICE ADDRESS
OF “0”.
SEE
INSTRUCTIONS.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE PRO-
TECTION ASSOCIATION’S STANDARD 74
(NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA 02269).
PRINTED INFORMATION DESCRIBING PROPER
INSTALLATION, OPERATION, TESTING,
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
RING
(GRAY)
TIP
(GREEN)
RING
(RED)
INCOMING
PHONE LINE
HANDSET
BLACK
RED
–
+
2000
OHMS
EOLR
2000
OHMS
EOLR
ZONE 1
ZONE 2
HI
LO
HI
LO
2000
OHMS
EOLR
2000
OHMS
EOLR
ZONE 3
ZONE 4
HI
LO
HI
LO
2000
OHMS
EOLR
2000
OHMS
EOLR
ZONE 5
ZONE 6
HI
LO
HI
LO
2000
OHMS
EOLR
2000
OHMS
EOLR
ZONE 7
ZONE 8
HI
LO
HI
LO
• MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS
(PLUS EOLR)
• RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC
(PROGRAMMABLE)
VISTA-20
SE
SUMMARY OF CONNECTIONS
CONNECTOR
FOR
PARTITION 2
KEYPAD(S)
YEL
RED
BLK
GRN
ALARM DEVICE MANUFACTURING CO.
A DIVISION OF PITTWAY CORPORATION
165 Eileen Way, Syosset, New York 11791
Copyright © 1997 PITTWAY CORPORATION
GEL LEAD ACID TYPE.
BATTERY NORMALLY NEED NOT BE
REPLACED FOR AT LEAST 3 YRS.
BATTERY CAPACITY FOR EMERGENCY
STANDBY USE AT LEAST 4 HOURS.
TO DETERMINE TOTAL STANDBY
LOAD ON BATTERY, ADD 100mA TO
TOTAL OF AUX. POWER OUTPUT
AND REMOTE KEYPAD CURRENTS.
USE UL LISTED
LIMITED ENERGY
CABLE FOR ALL
CONNECTIONS
BATTERY FUSE
FOR REPLACEMENT,
USE SAME VALUE
(e.g. ADEMCO No. 90-12)
9-PIN CONNECTOR
USED FOR 4300
TRANSFORMER
CONNECTIONS (FOR
OPTIONAL POWER LINE
CARRIER DEVICES)
SEE INSTRUCTIONS.
123456789
USE 4142TR CABLE
REMOTE
KEYPAD
PARTITION 2
USE 4300 TRANSFORMER INTERFACE
IN PLACE OF 1321 WHEN POWER LINE
CARRIER DEVICES ARE BEING USED
(SEE INSTRUCTIONS FOR
CONNECTIONS)
TIP
(BROWN)
}
}
CAN BE USED FOR GLASS BREAK DETECTORS
OPTIONAL:
No. 5800TM
TRANSMITTER MODULE (20mA)
(for No. 5827BD
Wireless Bidirectional Console)
AND/OR
No. 4285 VOICE MODULE (160mA)
AND/OR
No. 7720 PLUS/7820
LONG RANGE RADIO
MAY ALSO BE CONNECTED. SEE
INSTRUCTIONS ACCOMPANYING
THOSE DEVICES.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
COMPLIES WITH FCC RULES, PART 68.
FCC REGISTRATION NO. AC398U-68192-AL-E
RINGER EQUIVALENCE: 0.7B.
FOR COMPLETE INFORMATION
SEE INSTRUCTIONS N7526V4
WEEKLY TESTING IS REQUIRED TO ENSURE
PROPER OPERATION OF THIS SYSTEM.
3A
N7525V4 Rev. C 7/97
ALARM OUTPUT
10.5-13.8VDC, 2A MAX. (700mA MAX. FOR UL
USAGE, INCLUDING AUX POWER)
STEADY FOR BURGLARY/PANIC, TEMPORAL
PULSE SOUNDING FOR FIRE (e.g. USE ADEMCO
No. 702 SIREN, OR 12V BELL). SEE INSTRUCTIONS.
Figure 22. VISTA-20SE SUMMARY OF CONNECTIONS