Vista Ademco -10SE Guía para resolver problemas Pagina 49

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 48
49–
*
33 ALARM BELL TIMEOUT 1
0 = No timeout
1 = 4 min
2 = 8 min
3 = 12 min
4 = 16 min
This field determines whether the external sounder will shut off after time
a
UL installations: must be set for a minimum of 4 min (option 1)
*
34 EXIT DELAY 7 | 0 7 | 0
00-99 = exit delay time for each partition in seconds
The system will wait the time entered before sounding an alarm if the exit
door is left opened after the system has been armed.
*
35 ENTRY DELAY 01 3| 0 3| 0
00-99 = entry delay time for each partition in secs. Part. 1 Part. 2
The system will wait the time entered before sounding alarm upon
entering.
UL installations: must be set for a maximum of 20 seconds
*
36 ENTRY DELAY 02 6| 0 6| 0
00-99 = entry delay time for each partition in secs. Part. 1 Part. 2
The system will wait the time entered before sounding alarm upon
entering.
UL installations: must be set for a maximum of 20 seconds
*
37 AUDIBLE EXIT WARNING 1 1
0 = no exit warning sound Part. 1 Part. 2
1 = provide exit warning sound when armed AWAY
Warning sound consists of slow continuous beeps until last 5 seconds,
when it changes to fast beeps. The warning sound will end at the
termination of Exit time.
*
38 CONFIRMATION OF ARMING DING 0 0
0 = no ding Part. 1 Part. 2
1 = confirmation ding after arming system
2 = confirmation ding after arming from RF button or RF keypad only
(ding occurs when the system receives the RF transmission.)
Confirmation of arming is 1/2 second external sounder “ding” when
closing report is sent, or at the end of exit delay.
*
39 POWER UP IN PREVIOUS STATE 1
0 = always power up in a disarmed state
1 = assume the system status prior to power down
When the system powers up armed, an alarm will occur 1 minute after
arming if a zone is faulted.
Note that if the previous state was armed AWAY or STAY, the system will
not respond to sensor changes for 1 minute, which allows time for sensors
such as PIRs to stabilize.
UL installations: must be 1 (power up in previous state)
Vista de pagina 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 99 100

Comentarios a estos manuales

Sin comentarios